Onis Visa Diesel Generators

V250GXHD | 250 kVA - 275 kVA | VOLVO-PENTA | MJB250LB4


V250GXHD 250 kVA - 275 kVA VOLVO-PENTA MJB250LB4 Diesel Generator
Get a Quote on a V250GXHD VOLVO-PENTA Generator
TAD734GEAdvanced Engine Data

TAD734GEAdvanced Alternator Data

V250GXHD Specifications
General Data
Model V250GXHD
Prime kVA 250 kVA
Prime kW 192,00 kW
Standby kVA 275 kVA
Standby kW 212,00 kW
Power Factor 0.8
Voltage (VAC) 400/230 V
Frequency 50 Hz
Phases Three Phases (with Neutral)
Engine Speed 1500 rpm
Exhaust Model MSR/a 80
Exhaust Quantity 1
Exhaust Quantity 1
Exhaust Diameter 89 mm
Base Model GV100
Battery Capacity 100 Ah
Battery Quantity 1
Battery Voltage 12 V
Flexible Model DN75
Flexible Quantity 1
Flexible Diameter 89 mm
Dimensions, Weight & Tank Capacity
Length 3060 mm
Width 1140 mm
Height 2170 mm
Weight 2560 kg
Tank Capacity 360 l
Noise
Silent Canopy @ 7m (dBA) 68
Engine Data
Brand VOLVO-PENTA
Model TAD734GE
Continuous Power 250 kVA
Standby Power 275 kVA
RPM 1500 rpm
Electronic Governor Standard
Cooling Water
Air Intake Turbocharged
Cylinders 6
Cubic Capacity (l) 7,15 l
Precision Class N/A
Flywheel Power (kWm) 216 kW
BMEP (kPa)
Weight (kg) 764 kg
Antifreeze q.ty: 32 l
Oil qty (l) 29 l
Heat to radiation (kW) 111 kW
Heat to exhaust (kW) 160 kW
Heat to coolant (kW) 24 kW
Exhaust temperature (°C) 495 °C
Cooling air flow (m3/min) 312 m³/min
Combustion air flow (m3/min) 16,1 m³/min
Exhaust gas flow (m3/min) 33 m³/min
TA Luft emissions Not available
TA Luft 2000 emissions Not available
EPA emissions Not available
Stage STAGE II
SAE 2-11½
Fuel Consumption
25% Load 15,8 l/h
50% Load 30,1 l/h
75% Load 42,1 l/h
100% Load 52,8 l/h
110% Load 59,2 l/h
Alternator Data
Brand MARELLI
Model MJB250LB4
Contin. Power (H cl.kVA) 240,00 kVA
Contin. Power (H cl.kW) 192,00 kW
Stand by power (kVA) 265,00 kVA
Stand by power (kW) 212,00 kW
AVR Model M16FA655A
IP protection 23
Precision (+/- %) 0,5
Connection Stella Series
Phases Three Phases (with Neutral)
Winding Code M0
Lead No 12
Weight (kg) 710 Kg