Onis Visa Diesel Generators

V450GXHD | 450 kVA - 495 kVA | VOLVO-PENTA | MJB315MB4


V450GXHD 450 kVA - 495 kVA VOLVO-PENTA MJB315MB4 Diesel Generator
Get a Quote on a V450GXHD VOLVO-PENTA Generator
TAD1345GEAdvanced Engine Data

TAD1345GEAdvanced Alternator Data

V450GXHD Specifications
General Data
Model V450GXHD
Prime kVA 450 kVA
Prime kW 360,00 kW
Standby kVA 495 kVA
Standby kW 396,00 kW
Power Factor 0.8
Voltage (VAC) 400/230 V
Frequency 50 Hz
Phases Three Phases (with Neutral)
Engine Speed 1500 rpm
Exhaust Model MSR/a 125
Exhaust Quantity 1
Exhaust Quantity 1
Exhaust Diameter 140 mm
Base Model GV150
Battery Capacity 120 Ah
Battery Quantity 2
Battery Voltage 24 V
Flexible Model DN125
Flexible Quantity 1
Flexible Diameter 140 mm
Dimensions, Weight & Tank Capacity
Length 4000 mm
Width 1300 mm
Height 2414 mm
Weight 4900 kg
Tank Capacity 950 l
Noise
Silent Canopy @ 7m (dBA) 68
Engine Data
Brand VOLVO-PENTA
Model TAD1345GE
Continuous Power 451 kVA
Standby Power 501 kVA
RPM 1500 rpm
Electronic Governor Standard
Cooling Water
Air Intake Turbocharged
Cylinders 6
Cubic Capacity (l) 12,78 l
Precision Class G3
Flywheel Power (kWm) 388 kW
BMEP (kPa)
Weight (kg) 1325 kg
Antifreeze q.ty:
Oil qty (l) 36 l
Heat to radiation (kW) 145 kW
Heat to exhaust (kW) 268 kW
Heat to coolant (kW) 15 kW
Exhaust temperature (°C) 475 °C
Cooling air flow (m3/min) N/A
Combustion air flow (m3/min) 26,8 m³/min
Exhaust gas flow (m3/min) N/A
TA Luft emissions Not available
TA Luft 2000 emissions Not available
EPA emissions Not available
Stage STAGE II
SAE 1-14
Fuel Consumption
25% Load 25,1 l/h
50% Load 46 l/h
75% Load 68,2 l/h
100% Load 90,5 l/h
110% Load 100,6 l/h
Alternator Data
Brand MARELLI
Model MJB315MB4
Contin. Power (H cl.kVA) 450 kVA
Contin. Power (H cl.kW) 360 kW
Stand by power (kVA) 495 kVA
Stand by power (kW) 396 kW
AVR Model
IP protection 23
Precision (+/- %) 0,5
Connection Stella Series
Phases Three Phases (with Neutral)
Winding Code
Lead No 12
Weight (kg)