Onis Visa Diesel Generators

V505GXHD | 490 kVA - 556 kVA | VOLVO-PENTA | MJB355SA4


V505GXHD 490 kVA - 556 kVA VOLVO-PENTA MJB355SA4 Diesel Generator
Get a Quote on a V505GXHD VOLVO-PENTA Generator
TAD1641GEAdvanced Engine Data

TAD1641GEAdvanced Alternator Data

V505GXHD Specifications
General Data
Model V505GXHD
Prime kVA 490 kVA
Prime kW 392,00 kW
Standby kVA 556 kVA
Standby kW 444,80 kW
Power Factor 0.8
Voltage (VAC) 400/230 V
Frequency 50 Hz
Phases Three Phases (with Neutral)
Engine Speed 1500 rpm
Exhaust Model MSR/a 150
Exhaust Quantity 1
Exhaust Quantity 1
Exhaust Diameter 168 mm
Base Model GV200
Battery Capacity 100 Ah
Battery Quantity 2
Battery Voltage 24 V
Flexible Model DN150
Flexible Quantity 1
Flexible Diameter 168 mm
Dimensions, Weight & Tank Capacity
Length 4500 mm
Width 1840 mm
Height 2540 mm
Weight 6300 kg
Tank Capacity 950 l
Noise
Silent Canopy @ 7m (dBA) 68
Engine Data
Brand VOLVO-PENTA
Model TAD1641GE
Continuous Power 505 kVA
Standby Power 556 kVA
RPM 1500 rpm
Electronic Governor Standard
Cooling Water
Air Intake Turbocharged
Cylinders 6
Cubic Capacity (l) 16,12 l
Precision Class G3
Flywheel Power (kWm) 430 kW
BMEP (kPa)
Weight (kg) 1480 kg
Antifreeze q.ty: 93 l
Oil qty (l) 48 l
Heat to radiation (kW) 30 kW
Heat to exhaust (kW) 326 kW
Heat to coolant (kW) 172 kW
Exhaust temperature (°C) 475 °C
Cooling air flow (m3/min) 365 m³/min
Combustion air flow (m3/min) 32 m³/min
Exhaust gas flow (m3/min) 79 m³/min
TA Luft emissions Standard
TA Luft 2000 emissions Not available
EPA emissions TIER 2
Stage STAGE II
SAE 1-14
Fuel Consumption
25% Load 30 l/h
50% Load 51 l/h
75% Load 75 l/h
100% Load 101 l/h
110% Load 112 l/h
Alternator Data
Brand MARELLI
Model MJB355SA4
Contin. Power (H cl.kVA) 510 kVA
Contin. Power (H cl.kW) 408 kW
Stand by power (kVA) 560 kVA
Stand by power (kW) 448 kW
AVR Model
IP protection 23
Precision (+/- %) 0,5
Connection Stella Series
Phases Three Phases (with Neutral)
Winding Code
Lead No 12
Weight (kg)